Transformers and Transmission

“Derive transformer ratios from shared magnetic flux, then use energy conservation to analyse loads and transmission losses.”

Learning Objectives

• Explain mutual induction between insulated windings. • Derive ideal voltage and current ratios with explicit assumptions. • Analyse loading, efficiency and the limits of DC operation. • Explain transformer losses and the advantage of high-voltage transmission.

Two circuits connected through a changing magnetic field

A transformer has primary and secondary windings insulated electrically from each other and coupled magnetically through a core. An alternating primary voltage produces changing core flux. That flux links the secondary turns and induces an emf even though no conduction wire connects the two windings. A closed secondary load then receives current and energy. A transformer changes AC voltage level; it does not create energy or change the source frequency in this model.

Shared flux ΦPrimary NpSecondary NsWindings are electrically insulated; turns are schematic.
Magnetic coupling between insulated windings— Schematic; labels describe the physical quantities.

The ideal model has negligible winding resistance, no leakage flux, no core dissipation and effectively negligible magnetising current. Both windings share the same flux per turn. Real transformers only approximate these conditions. The shared-flux assumption is the key to the turns ratio; energy conservation supplies the current ratio after a load is specified.

Induced emf per windingLaTeX
Np and Ns are dimensionless turn counts and Φ is flux in Wb per turn. Use consistent winding orientations for signed emfs. Wb s⁻¹ = V.

In an ideal winding the applied terminal voltage is balanced by its induced back emf in the loop. The back emf opposes the applied drive under the chosen loop convention; equality of magnitudes must not erase that physical opposition. With negligible winding drops, the ratio of terminal RMS voltage magnitudes is the turns ratio. This remains the ideal loaded ratio as well as the no-load ratio; real loading can produce voltage regulation errors.

Ideal terminal voltage ratioLaTeX
Vp and Vs are RMS voltage magnitudes and a is the turns ratio. Ns > Np steps voltage up; Ns < Np steps it down. Peak ratios are identical for sinusoidal operation.

Why stepping up voltage steps down load current

Connect a resistive load to the secondary. For a lossless transformer input real power equals output real power. A resistor has unity power factor, so VpIp = VsIs. Substituting Vs = aVp gives Ip = aIs, or Is/Ip = 1/a. For an ideal transformer with a reactive load, the load phase is reflected to the primary and the current-magnitude ratio remains reciprocal when magnetising current is neglected; equality of real powers alone requires including the power factors.

Ideal load-current and resistance reflectionLaTeX
The resistance expression assumes a secondary resistor Rs, for which Is = Vs/Rs. Substitute Vs = aVp and Ip = aIs to obtain Ip = a²Vp/Rs. This describes the load seen at the primary, not winding-wire resistance.

The transformer does not independently dictate an arbitrary secondary current. Its voltage and the connected load determine Is; the primary then draws the corresponding load current. With an open secondary, Is = 0. A real transformer still takes a magnetising current and supplies core losses. In the ideal limiting model these no-load contributions are neglected. Calling the primary current “small” under every load would therefore be misleading.

A loaded step-down transformer

Problem
An ideal transformer has Np = 1000 and Ns = 100, with 230 V RMS primary and a 4.6 Ω resistive secondary load. Find both currents and powers.

  1. 1.a = 0.10, so Vs = 23.0 V. Is = Vs/Rs = 23/4.6 = 5.00 A.
  2. 2.Ip = aIs = 0.500 A. Output power = 23 × 5 = 115 W, equal to input 230 × 0.500 = 115 W.
  3. 3.The input sees Rin = 100 × 4.6 = 460 Ω, which checks 230/0.500. The secondary current is ten times larger because its voltage is ten times smaller.

Why steady DC does not work

A steady magnetic flux produces no secondary emf. Applying steady DC to a real primary can initially change flux and induce a switching response, but it does not sustain the intended alternating flux. With little winding resistance and no ongoing inductive opposition in the settled linear DC model, current can become excessive; core saturation can worsen it. Thus an ordinary mains-frequency transformer is not operated directly on steady DC. Electronic converters can switch DC to produce changing flux, which is a different input waveform and system.

Real losses and their reduction

EffectPhysical consequenceCommon reduction
Winding resistanceI²r heating in copperLow-resistance wire; thicker conductors for high current
Eddy currentsInduced circulating currents heat the coreThin insulated laminations increase loop resistance
HysteresisRepeated magnetisation dissipates energy per cycleUse a low-loss soft magnetic core material
Leakage fluxIncomplete coupling and voltage regulation effectsClose winding coupling and suitable core design

Flux leakage primarily represents imperfect coupling and leakage inductance, not automatically an irreversible heat loss by itself. It can reduce useful voltage transfer and contribute indirectly to additional losses in a practical design. Hysteresis and eddy currents are genuine core heating mechanisms. Laminations reduce eddy-current paths; they do not remove the desired alternating flux.

Efficiency uses real powerLaTeX
η is dimensionless and often quoted as a percentage. Use real power including power factor when necessary, not an unqualified ratio of VA ratings.
Accounting for nonideal efficiency

Problem
A transformer supplies 12 V RMS at 5 A to a resistive load with 90% efficiency. Find input real power and losses.

  1. 1.Pout = 12 × 5 = 60 W. Pin = 60/0.90 = 66.7 W.
  2. 2.Ploss = 66.7 − 60 = 6.7 W. Efficiency does not by itself specify primary RMS current without input voltage and input power factor.
  3. 3.If Vp = 240 V RMS and primary power factor is explicitly unity, Ip = 66.7/240 = 0.278 A. This conditional calculation avoids silently assuming away reactive current.

High voltage reduces transmission heating

For fixed transmitted real power and power factor, increasing RMS voltage reduces current in inverse proportion. A transmission line loses I²r, so stepping voltage up by a factor k reduces this heating by k² under those fixed conditions. Step-down stages then provide suitable local supply voltage. Insulation and equipment requirements limit the choice. AC historically enabled convenient transformer-based voltage conversion; modern DC transmission can also be efficient with converters, so AC is not universally superior for every distance and application.

The same power through a line

Problem
Deliver 100 kW at unity power factor through a line of total resistance 2 Ω. Compare load-side voltages 1 kV and 10 kV, assuming each is maintained.

  1. 1.At 1 kV, I = 100000/1000 = 100 A, so line heating is 100² × 2 = 20 kW.
  2. 2.At 10 kV, I = 10 A and heating is 10² × 2 = 200 W. Increasing voltage tenfold reduces heating one hundredfold.
  3. 3.These numbers treat specified load voltage as maintained and neglect transformer losses. The sending source supplies the load power plus line loss; voltage conversion has not supplied free energy.

Quick Quiz

Quiz

Quick check

A transformer secondary emf arises from

Explanation: Faraday’s law relates induced emf to flux change.

Quick check

Ns/Np = 4 in an ideal transformer gives Vs/Vp equal to

Explanation: Voltage magnitudes scale with turns.

Quick check

For a loaded lossless ideal transformer, doubling output voltage relative to input gives output current

Explanation: The current ratio is reciprocal to the turns ratio, for the load-current component.

Quick check

Core laminations principally reduce

Explanation: They interrupt conducting loops inside the core.

Quick check

At fixed P and power factor, raising line voltage tenfold reduces resistive loss by

Explanation: Current falls tenfold and I²r falls one hundredfold.

Practice Problems

Practice Problems
  1. An ideal transformer has 100 primary turns and 200 secondary turns. Primary voltage is 220 V RMS and primary load current 10 A. Find output voltage, current and power.
  2. A 240 V to 24 V ideal transformer feeds a 12 Ω resistor. Find currents and reflected resistance.
  3. A transformer has 500 W real input and 460 W real output. Find efficiency and explain where the rest goes.
  4. Explain why connecting an ordinary low-resistance primary directly to steady DC is unsuitable.
  5. For the same maintained delivered power and power factor, line voltage triples while total line resistance doubles. Find the ratio of line loss.

a = 2, so Vs = 440 V. Is = Ip/a = 5.0 A. At unity load power factor, input and output powers both equal 2200 W. For a reactive load the real powers are instead 2200 times the shared ideal power factor.

Key Takeaways

Key Takeaways

• A transformer couples insulated circuits through changing shared magnetic flux. • Ideal voltage magnitudes follow the turns ratio. • Ideal load-current magnitudes follow the reciprocal turns ratio. • The load determines output current; the primary supplies corresponding energy. • Ordinary transformers do not sustain transformation from steady DC. • Real windings and cores dissipate energy, so efficiency is below unity. • At fixed delivered power and power factor, high line voltage reduces I²r loss.