Alternating Current · Lesson 7 of 9
AC Power and Power Factor
“Derive average AC power and explain why reactive current can increase transmission losses without delivering extra useful power.”
• Derive mean power for sinusoidal voltage and current. • Distinguish instantaneous, average and apparent power. • Calculate power factor and energy dissipation. • Explain parallel capacitive correction of an inductive load.
Current alone does not determine delivered power
Two loads can draw the same RMS current from the same RMS voltage and absorb different mean powers. For a resistor, voltage and current have the same sign at every instant, so energy continually enters it. With reactive elements, the voltage-current timing sometimes makes their product negative: energy returns from stored fields. The signed product must be averaged; multiplying RMS magnitudes alone omits this timing information.
The second cosine completes two cycles during each source cycle and has zero mean. The constant term survives. Since VmIm/2 = (Vm/√2)(Im/√2), the surviving product can be expressed using RMS values. This derivation requires sinusoidal voltage and current at a common frequency; a distorted load needs the actual average of vi, and cosφ alone may not give its full power factor.
The product S = VI is apparent power, measured in volt-amperes (VA). P/S is the power factor; for these sinusoidal circuits it equals cosφ. For fixed V and I, unity power factor gives the largest real power. This statement must specify what stays fixed: changing the circuit may also change I. A smaller phase angle does not guarantee the same numerical power under every possible constraint.
| Load | Phase in our convention | Mean power |
|---|---|---|
| Pure resistance | φ = 0 | VI = I²R |
| Ideal inductance | φ = +90° | 0 |
| Ideal capacitance | φ = −90° | 0 |
| Passive series LCR | tanφ = (XL − XC)/R | VI cosφ = I²R |
| Series LCR at resonance | φ = 0 | V²/R at fixed source V |
A purely reactive current is sometimes called wattless because it produces no mean absorption in the ideal reactive element. It is still a real measurable current. It can heat resistance in wires and windings elsewhere. In a general passive LCR load the mean absorbed power is nonnegative, but its instantaneous power can become negative. An active circuit can even return net energy; the nonnegative-average statement is not a universal law for every electrical device.
Problem
A 200 V RMS source drives a series circuit with R = 3 Ω and net inductive reactance 4 Ω. Find P, S and power factor.
- 1.Z = √(3² + 4²) = 5 Ω and I = 200/5 = 40 A. cosφ = R/Z = 0.600.
- 2.S = VI = 8000 VA, while P = VI cosφ = 4800 W. The independent check I²R = 40² × 3 = 4800 W agrees.
- 3.The 3200 numerical difference between VA and W is not an extra heat-loss term. Apparent power is a voltage-current rating, not an energy balance to subtract from real power.
Why a low power factor increases line loss
Suppose a load needs fixed real power P at fixed RMS terminal voltage V. Its line current is I = P/(V cosφ). Lowering power factor requires a larger RMS current. A supply line of resistance r then wastes I²r, even though the ideal reactive part of the load itself has zero mean power. Keep the load resistance R separate from line resistance r: they describe different places where energy becomes heat.
Correcting an inductive load in parallel
An inductive load current lags the supply voltage. Resolve its current phasor into an in-phase component IP = I cosφ and a lagging perpendicular component IQ = I sinφ. The first supplies real power; the second represents reactive exchange. Connect an ideal capacitor in parallel across the same supply so its leading current cancels the lagging perpendicular component. The line then supplies only the in-phase resultant when correction is exact.
This is not the same construction as inserting a series capacitor to make XL = XC. In parallel correction, branch currents add and the original load impedance need not change. The simple R/Z expression should not be applied to the whole parallel network using the original series load R and Z. Practical correction needs suitable voltage ratings and may interact with harmonics; the calculation here is an ideal sinusoidal model.
Problem
A load draws 10 A at 230 V RMS, 50 Hz and lagging power factor 0.8. Calculate the ideal parallel capacitance for unity line power factor.
- 1.φ has cosφ = 0.8, so sinφ = 0.6. IP = 8 A and lagging IQ = 6 A. Real load power is 230 × 10 × 0.8 = 1840 W.
- 2.A capacitor taking 6 A leading gives C = 6/[2π(50)(230)] = 83.0 μF. Line current becomes 8 A; the original load branch still takes 10 A.
- 3.If the line resistance is 0.5 Ω, its heat loss falls from 10² × 0.5 = 50 W to 8² × 0.5 = 32 W. The capacitor does not supply the 1840 W; the source still does.
Quick Quiz
Quiz
For sinusoidal voltage and current, mean real power is
Explanation: Averaging the product retains the cosine of their phase separation.
A pure capacitor can draw current while mean power is zero because
Explanation: The cycle-integrated change of stored electric energy is zero.
At fixed P and V, halving power factor changes line I²r loss by
Explanation: Current doubles and its square quadruples.
An ideal parallel correction capacitor supplies
Explanation: It cancels the load’s lagging perpendicular current component.
Negative instantaneous passive power means
Explanation: Stored energy can be released even when the cycle mean is positive.
Practice Problems
- A 240 V RMS load draws 5 A with power factor 0.60. Find apparent power, real power and energy absorbed in 10 min.
- At one frequency a series circuit has R = 30 Ω and Z = 50 Ω with I = 4 A RMS. Find power factor and real power, and say whether lead or lag can be inferred.
- A fixed 1000 W load uses 200 V RMS through a 1 Ω line. Compare line loss at power factors 1 and 0.5, assuming maintained load voltage.
- A 100 V RMS, 50 Hz load current has 3 A in phase and 4 A lagging perpendicular to voltage. Find a parallel correction capacitor and corrected line current.
- Show why the cycle average of p = (VmIm/2)[cosφ − cos(2ωt − φ)] is not obtained by setting t = 0.
S = VI = 1200 VA. P = 1200 × 0.60 = 720 W. Energy = Pt = 720 × 600 = 432000 J = 0.120 kWh. Use real power, not apparent power, for energy.
Key Takeaways
• Mean sinusoidal power is VI cosφ using RMS values. • Apparent power VI is measured in VA, while real power is measured in W. • Only total resistance dissipates power in the ideal series LCR model. • Negative instantaneous power describes stored energy returning. • Wattless current can still cause heating in resistive supply wires. • For fixed delivered power and voltage, low power factor raises line current and loss. • A parallel capacitor can cancel a lagging reactive current component.
Finished this lesson? Mark it complete to track your progress.